REG216/
REG216 Compact
1MRB520004-Ben
Page 1
Issued: November 1999Changed: since July 1998
Data subject to change without notice
REG216 System
REG216 Compact
•Display of event, their acknowledgment and printout•Disturbance recording•Self-documentation•Long-term stability
•Communication and coordination with sta-tion control•Two design versions available; extended version or compact version (with or without cubicle)
Features
•Modular hardware
•Selectable protection functions•Multitude of applications•Menu-assisted setting with PC•Fully numerical signal processing•Continuous self-monitoring of hardware•Cyclical testing routines
•Setting of parameters and recording of the settings by PC•Display of measured values
Application
The REG216/REG216 Compact system is intended for the protection of generators and block transformers.
The modular hardware and software design allows an extremely flexible installation. Simplicity of adaption to the size of the pri-mary system and the desired protection schemes are achieved through the combi-nation of a software library and hardware modules.
Economic solutions can thus be achieved in the full range of applications for which it is intended.
The REG216 software system offers a library of protective functions. Functions suitable for generator and transformer protection are listed in the table below.
Different degrees of redundancy can be selected. Availability and reliability of the protection can be chosen to suit the applica-tion by duplicating e.g. auxiliary supply units of the whole system.
Standard interfaces make REG216/REG216 Compact compatible with different process control systems. Data exchange with higher process control levels are possible, e.g. one-way reporting of digital states and events, measured values and protection parameters.
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 2
Application (cont´d)
Protection functions:Generator differential
Power transformer differential
Definite time overcurrent (undercurrent)Overcurrent or undercurrent with peak valueevaluation
Restricted earth fault
Voltage-controlled overcurrentInverse time overcurrent
Negative phase sequence currentDefinite time overvoltage (undervoltage)
ANSIcode87 G87 T515087 N51-2751465927
Description
three-phase
three-phase for 2- and 3-winding transformers
definite time delay, for phase and earth-fault, over-and undercurrent
instantaneous operation or with definite time delay,
value evaluation wide frequency range, over- and undercurrentovercurrent operation with definite time delay*operation restrained by undervoltage
inverse current dependent time delay, for phase andearth fault
negative phase sequence current with definite time delay or inverse time delay with thermal replicadefinite time delay, over- and undervoltageApplicable also for
- stator E/F (95%) (59 G/N)- rotor E/F ( R) **
- intertum fault protection
based on the displacement principle calculation of theearth fault resistance.
in addition the units REX010 and REX011 are required
circular characteristics centered at origin of impedance planecircular characteristics for loss of excitation protection
detecting loss of synchronism of a generator as against the net-work
any characteristic angle, over and underpower for:- active power- reactive power
- reverse power protection- minimum forward power
thermal replica with operating characteristicaccording to ASA-C50.13*** for:- standard stator current (49 S)- rotor current (49 R)
evaluation of negative phase sequence of currentsinverse time delay;with terminal replica
thermal protection with precise thermal replica
evaluation of voltage inputdf/dt
voltage/frequency protection
definite time delay or inverse time delay
monitoring/comparing two groups of single- or three-phase volt-age
instantaneous operation with definite time delay
supervision of phase angle frequency and voltage level of two systems
AND, OR, flip-flop, time delay, counter
*with external hardware: stabilizing resistor, voltage-dependent resistor
**with external hardware: measuring bridge YWX111-..., coupling condensers***ASA = American Standard Association
Aside from these typical generator protection functions the entire library of the RE.316*4 platform is also available (e.g. distance protection, autoreclosure, I0 inverse, etc.). For more details see manual of REG216.
100% stator and rotor earth faultprotection
UnderimpedanceMinimum reactancePole slip protectionPower
S R21407832
Overload49
Negative phase sequence current46
Overtemperature
Frequency
Rate-of-frequency changeOverexcitationVoltage balance
Voltage peak value evaluationSynchro checkLogical functions
498181246059,2725
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 3
Protection functions
All protection functions required for the stand-alone protection of generators, power transformers and feeders are available. The system therefore replaces several relays of a conventional protection scheme for such power system equipment. The table on page 2 gives a survey of the most significant protec-tion functions.
The desired protection functions to suit the particular application can simply be selected from a comprehensive library using the per-sonal computer. No knowledge of computer programming is required.
All setting ranges are extremely wide to make the protection functions suitable for a multi-tude of applications. The following main parameters can be set:
•Allocation of processing units•Input channel or channels•Pick-up setting•Time delay
•Definition of the operating characteristic•Tripping logic•Control signal logic
Setting a corresponding parameter enables the protection functions to be \"connected\" to particular input channels.
Digital input and output signals can also be internally combined logically:
•The tripping outputs of each protection function can be assigned to channels of the tripping auxiliary relay assembly in a man-ner corresponding to a matrix.•The pick-up and tripping signals can be assigned to the channels of the signalling auxiliary relay assembly.•Provision is available for blocking each protection function with a digital signal (e.g. digital inputs or by using the tripping signal of another protection function).•External signals applied to the digital inputs can be processed in any desired fashion.•Digital signals can be combined to per-form logical functions e.g. external en-abling or blocking signals with the output signals of an internal protection function and then used to block one of the other protection functions.
ConstructionHardware
There are two different versions available: REG216 and REG216 Compact. The REG216 equipment comprises two main assemblies which are physically separated from each other and linked by standard pre-fabricated screened cables:
•Interfaces to the primary system (CT’s, PT’s and auxiliary relays), which provide dc isolation and a barrier to electromag-netic interference.•Parallel bus and associated electronic units (e.g. analogue inputs and data processors/ for signal conditioning and processingThe complete protection scheme comprises relatively few hardware modules allowing subsequent expansion of electronic units and the interfaces. 21 units of rack space is avail-able per equipment frame.
Excellent electromagnetic compatibility has been achieved through careful attention to physical separation of the interfaces from the signal processing units
All hardware can be accommodated in one cubicle, which provides a further screen against induced interference and affords physical protection against dust, etc.REG216C is a standard compact rack ver-sion, available in 7 versions, with a limited number of I/O's but equipped with the same SW library as the REG216 system.
Other protection relays for functions which are not part of the REG216/REG216 Com-pact system may be installed in the cubicle and correspondingly interwired with REG216/REG216 Compact.
Interfaces to the primary system
The following modular assemblies provide interfacing of REG216 to the power system.
Input transformer assembly 216GW61
This assembly adjusts the signal levels and provides isolation between the primary sys-tem CT and PT circuits and the electronic cir-cuits of the protection. One type of PT and two types of CT’s are available, to meet dif-ferent accuracy and dynamic performance requirements.
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 4
Construction (cont´d)
Space is available for up to 12 transformers, which are selected to suit the application. Up to four assemblies can be used, i.e. 48 inputs.
Input auxiliary relay assembly 216GE61
Auxiliary relay and optocoupler assembly 216GD61a
Up to 16 auxiliary relays can be accommo-dated, providing complete potential separa-tion of digital input signals.
Output auxiliary relay assembly 216GA61
This assembly is used in the compact version REG216. It provides eight tripping relays, each with two powerful, potential-free trip-ping contacts (with surge circuits), 16 auxil-iary relays and 16 optocoupler input circuits. Max. four assemblies can be provided.
Parallel bus and electronic units
Up to 16 auxiliary relays can be accommo-dated providing complete potential separation of digital output signals (two contacts per sig-nal).
Tripping auxiliary relay assembly 216GA62
Up to eight powerful, potential-free tripping contacts and circuits, which provide high-speed operation (surge circuit) with reduced consumption after operation (economy cir-cuit) are provided.
Facilities for different trip circuit supervision arrangements in conjunction with the output unit 216DB61and the input auxiliary relay assembly 216GE61 (option) are also pro-vided.
The tripping auxiliary relay assembly can be optionally fitted with a tripping logic diode matrix to enable direct coupling of external signals. REG216 can also read and process external signals via digital inputs.
The electronic units are of plug-in design and accommodated in an equipment rack with the standard dimension 19\mm). An equipment rack of this kind is divided into 21 standard divisions. The
exchange of data via the parallel bus B448C is controlled and monitored by all units avail-able.
The protection system is based on a data bus with digital signal processing for most func-tions; signal conditioning, analogue and digi-tal inputs, A/D conversion, processing and signal output.
The components of the system are:
•Static plug-in units, which exchange data via a powerful parallel bus.
•Interfaces to the process (primary system, station equipment), which are isolated from the digital processing unit.
Transformer unitGW61A / DEA61bCPUVC62aPC carde.g.LONBinaryoutputDB61Signal relaysGA61BinaryoutputAB61Tripping relaysGA62TripDB61DC / DCNG61,2,3CPUVC62aPC cardSPALONSMSSCSInput relaysGE61Fig. 1Configuration of the REG216 protection system
Numerical generator protection
Equipment rack 216MB66/216MB68 and parallel bus B448C
The main features of the parallel bus B448C are:
•Specification based on IEEE P 6 (future bus).
•Time multiplexing of addresses and data (16 bit).
•Asynchronous data transmission with handshake.
•Integrity checking of each data exchange.•Up to 32 master units having equal status, actively accessing the bus.
•Common internal 24V auxiliary supply for all electronic units; redundant 24V are possible.
Processing unit 216VC62a
•32 bit processor type 80486DX-2•Application software on Flash EPROM•Operating data on RAM
•Settings on non-volatile Flash EPROM•Potential-free RS-423 interface for PCoperation•Connection to the station control with transmission of messages•Time clock synchronizing for time-tagging of events•Non-volatile event and disturbance mem-ory (gold capacitor buffered) •Space requirement: two rack divisions
Analogue Input unit 216EA61b
•24 inputs sampled simultaneously in groups of six•Sampling frequency 600 (720) Hz for a power frequency of 50 (60) Hz•Space requirement: two rack divisions
Digital output unit 216AB61
•32 outputs for controlling the relays of the output auxiliary relay assembly•Short-circuit proof
•Front plate LED’s for indication of acti-vated relays•Space requirement: one rack division
Binary and analog output unit 216AC61
•16 binary outputs for controlling of the output auxiliary relay assembly-Short-circuit proof
-Front plate LED’s for marking activated relays
REG216/ REG216
Compact
1MRB520004-Ben
Page 5
•8 analog outputs (0 . . . 20 mA without gal-vanic separation)•Front space requirements: one rack divi-sion
Binary input unit 216EB61
•32 binary inputs used to connect ON or OFF signals to the REG216 protection sys-tem from input relay assembly•Time-tagging with a resolution of 1 ms•Front plate LED’s marking activated relays•Front space requirements: one rack divi-sion
Tripping output unit 216DB61
•8 outputs for two-pole control of auxiliary tripping relays•Monitored output amplifiers
•16 digital inputs for the signals from the input auxiliary relay assembly (two each can be used to externally enable and block tripping respectively)•Activated outputs and inputs indicated by LED’s•Front space requirements: one rack divi-sion
Auxiliary dc supply unit 216NG61, 216NG62 and 216NG63
•Versions for 36 to 312 V dc input•Outputs 24V dc, 150 W
•Short-circuit and overload-proof outputs•Parallel connection to increase rating•Parallel connection for redundancy(2 outputs)•Space requirement: 3 rack divisionsAll the REG216 protection functions operate with sampled primary system voltages and currents. The sampling rate of the analogue input units is 12 times per period at rated power system frequency with a dynamic range of 15 bits.
All further signal processing takes place digi-tally. The protection functions are therefore universally applicable, highly accurate and have excellent long-time stability.
Dc components and harmonic contents are efficiently suppressed by digital filters to avoid disturbance. The tripping logic for the
ABB Power Automation
Numerical generator protection
internal protection functions (earlier a diode matrix), is software-controlled in REG216/REG216 Compact.
Setting and control
The protection system is set and controlled using a personal computer connected to it via a serial interface. Operation of the console is menu-assisted and permits:
•Setting of parameters and recording of the settings
•Display of measured values
•Display of events, their acknowledgment and printout
•Disturbance recording (option)
Windows HMI (Option)
A new Windows-based setting tool RE.16 WIN-HMI is available since the Firmware version V5.2.This Software runs only under the following operating systems: •WINDOWS 95•WINDOWS 98•WINDOWS NT
The perfect tool for engineering, testing, commissioning and maintenance personnel can be used for ON-LINE or OFF-LINE pro-gramming.
For each protection function a visible tripping characteristic is displayed depending on the setting values, e.g. the underimpedance func-tion shown below.
REG216/ REG216
Compact
1MRB520004-Ben
Page 6
There is a library with all protection functions necessary for generator and transformer pro-tection. Easy activation of a protective func-tion bay “drag&drop” technology.
Self-monitoring and testing facilities
The self-monitoring and testing routine
philosophy can be divided into following sec-tions:
•Self-monitoring
•Parameter viewing facilities
•Injection testing with separate test equip-ment.
Self-monitoring
The self-monitoring and testing routine philo-sophy is quite different from conventional testing techniques. Whilst the previous prac-tice in protection was to maintain availability through comprehensive periodic testing. REG216/REG216 Compact does this contin-uously by taking full advantage of digital and data bus technology.
The self-monitoring functions have two ele-ments:
•Continuous self-monitoring by hardware•Cyclically executed testing routines, mainly by software.
Testing
Viewing protection measurements
One feature is the provision to view various operating measurements. This together with the self-monitoring functions replaces the periodic injection testing necessary with con-ventional protection equipment. The follow-ing data can be viewed:
a)The system values as measured by all pro-tection functions. The corresponding func-tions do not have to have picked up for this purpose.
ABB Power Automation
Construction (cont´d)
Numerical generator protection
b) Analogue inputs. The amplitudes, fre-quency and phase relationships of all the analogue inputs can be viewed without jeopardizing the operation of the protec-tion functions.c)Digital input and output signals. The status of each signal can be viewed.Apart from the self-monitoring routines, the fact that the measurement data can be viewed all the way from the input transformers to the digital signals also confirms the correct func-tioning of the digital processors and the data bus.
Using software HMI „Test functions“
The desired protective function may be se-lected from the list of available active func-tions. The test operation is based on simu-lated numerical values. One or more channels may be selected for testing the tripping or sig-
REG216/ REG216
Compact
1MRB520004-Ben
Page 7
nalling outputs. The test function is mainly used for commissioning purposes when the system is out of service.
Redundancy
Hardware and software redundancy is ad-apted to the functional requirements. Two independent groups of protection functions are accommodated in either two separate hardware racks (REG216) or in only one rack (REG216C), but with two completely inde-pendent hardware groups.
Injection testing
A 100% test of system can be carried out by injecting test voltages and currents using, for example, a test set type XS92a or FREJA. Provision is made for injection testing with a test set at the terminals of the input trans-former assembly 216GW61/216GW62. The terminals enable primary system PT circuits to be interrupted and CT’s to be short-cir-cuited.
ABB Power Automation
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 8
Technical data
Table 1:Input circuit
Rated current INRated voltage UNRated frequency fNThermal ratings:
continuousfor 10 sfor 1 s
surge (half-cycle)Burden of the current inputsBurden of the voltage inputsInput signals
acdc
1A,2Aor5A
100 V/110 V or 200 V/220 V50/60 Hz4 x IN30 x IN100 x IN
250 x IN (peak)<0.2 VA/input at IN<0.4 VA/input at UN24 V to 220 V24 V to 250 V
Table 2:Generator differential (87G)
Features:
-Three-phase function
-Current-adaptive characteristic
-High stability for external faults and current transformer saturationSettings:
g-setting (basic sensitivity)v-setting (slope)Max. trip time
- for I∆ > 2 IN- for I∆ ≤=2=IN
Accuracy of pick-up value of g
0.1 to 0.5 IN in steps of 0.05 IN0.25; 0.5≤=30 ms≤ 50 ms± 5% IN (at fN)
Table 3:Transformer differential (87T)
Features:
- For two- and three-winding transformers- Three-phase function
- Current-adaptive characteristic
- High stability for external faults and current transformer saturation
- No auxiliary transformers necessary because of vector group and CT ratio compensation- Inrush restraint using 2nd harmonicSettings:g-settingv-settingb-setting
Max. trip time (protected transformer loaded)
- for I∆ > 2 IN- for I∆=≤ 2 IN
0.1 to 0.5 IN in steps of 0.05 IN0.25, 0.5
1.25 to 2.5 in steps of 0.25≤ 30 ms≤ 50 ms
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 9
Accuracy of pick-up valueReset conditions
Differential protection definitions:
± 5% IN (at fN)I∆ < 0.8 g-setting
I∆ = I1+ I2 + I3 IH=
0
α== arg (I1'; - I2')2-winding:3-winding:
I1' = I1, I2' = I2I1' = MAX (I1, Ì2, Ì3) I2' = I1 + I2 + I3 - I1'I′⋅I′⋅cosα12
forcosα ≥0
for cos α <0
Fig. 2Differential protection characteristic
Table 4:Definite time overcurrent (51)
(optionally used as restricted earth fault relay by additional external hardware)Features:
- Maximum or minimum function (over- and undercurrent)- Single- or three-phase measurement
- Highest or lowest phase value evaluation for three-phase functionSettings:CurrentDelay
Accuracy of pick-up valueReset ratio
Max. trip time with no delay
0.02 to 20 IN in steps of 0.01 IN0.02 to 60 s in steps of 0,01 s± 5% (at fN)
> 94% (for max. function)< 106% (for min. function)≤ 60 ms
Table 5:Instantaneous overcurrent (50)
Features:
- Maximum or minimum function (over- and undercurrent)- Single- or three-phase measurements- Wide frequency range (0.04 to 1.2 fN)- Peak value evaluationSettings:CurrentDelay
Accuracy of pick-up value (at 0.08 to 1.1 fN)Reset ratio
Max. trip time with no delay (at fN)
0.1 to 20 IN in steps of 0.1 IN0 to 60 s in steps of 0.01 s±5%
>90% (for max. function)<110% (for min. function)≤ 30 ms
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 10
Technical data (cont´d)
Table 6:Voltage-controlled overcurrent (51-27)
Features:
- Maximum current value memorized after start- Reset of function after voltage return or after trip- Single- or three-phase measurement for current- Positive-sequence voltage evaluationSettings:CurrentVoltageDelayHold time
Accuracy of pick-up valueReset ratioStarting time
0.5 to 20 IN in steps of 0.1 IN0.4 to 1.1 UN in steps of 0.01 UN0.5 to 60 s in steps of 0.01 s0.1 to 10 s in steps of 0.02 s± 5% (at fN)> 93%≤ 80 ms
Table 7:Inverse time-overcurrent function (51)
Single or three-phase measurement with detection of the highest phase currentStable response to transients
Inverse time characteristic
(acc. to B.S. 142 with extended setting range)
normal inversevery inverse
extremely inverselong time earth faultor RXIDG characteristicSettings:
Number of phasesBase current IBPick-up currentMin. time settingk1 setting
Accuracy classes for the operating time
according to BritishStandard 142RXIDG characteristicReset ratio
1 or 3
0.04...2.5IN in steps of 0.01IN1...4IB in steps of 0.01IB0...10s in steps of 0.1s0.01...200s in steps of 0.01sE 5.0
±4% (1 - I/80 IB)95%
t=k1 / ((I/IB)C-1)c = 0.02c = 1c = 2c = 1
t = 5.8 - 1.35 · In (I/IB)
Table 8:Negative phase sequence current (46)
Features:
- Protection against unbalanced load- Definite time delay
- Three-phase measurementSettings:
Negative phase-sequence current (I2)Delay
Accuracy of pick-up valueReset ratioStarting time
0.02 to 0.5 IN in steps of 0.01 IN0.5 to 60 s in steps of 0.01 s
± 2% IN (at fN, I ≤ IN with measuring transformers)> 94%≤ 80 ms
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 11
Table 9:Definite time overvoltage (27, 59)
Features:
- Maximum or minimum function
- Single- or three-phase measurement
- Highest or lowest phase value evaluation for three-phase function- Also applicable as
- Stator earth fault (95%)(59G/N)- Rotor earth fault* (R)- Interturn faultSettings:VoltageDelay
Accuracy of pick-up valueReset ratioMin. trip time
0.01 to 2.0 UN in steps of 0.002 UN0.02 to 60 s in steps of 0.01 s± 3% (at fN, U > 0.1 UN)> 96% (for max. function)< 104% (for min. function)≤ 60 ms
*requires ext. hardware: measuring bridge YWX111-... and coupling condensers.
Table 10:Instantaneous overvoltage protection function (59, 27) with peak value
evaluation
Features:
- Evaluation of instantaneous values, therefore extremely fast and frequency-independent on a wide scale- Storing of the highest instantaneous value after start- No suppression of d. c. components- No suppression of harmonics- 1- or 3phase
- Maximum value detection for multi-phase functions- Variable lower limiting frequency fminSettings:VoltageDelayLimiting fminReset ratio
Min. trip time at no delay (at fN)
0.01 to 2.0 UN in steps of 0.01 UN0.00 to 60 s in steps of 0.01 s25 to 50 Hz in steps of 1 Hz> 90% (for max. function)< 110% (for min. function)< 30 ms (for max. function)
±5%Accuracy of pick-up value (at 0.08 to 1.1 fN) ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 12
Technical data (cont´d)Table 11:Underimpedance (21)
Features:
- Detection of two- and three-phase short circuits (back-up protection)- Single- or three-phase measurement
- Circular characteristic centered at origin of R-X diagram
- Lowest phase value evaluation for three-phase measurement
Fig. 3Settings:
Underimpedance protection function characteristics
0.025 to 2.5 UN/lN in steps of 0.001 UN/lN0.2 to 60 s in steps of 0.01 s< 107%< 80 ms (at fN)
ImpedanceDelayReset ratioStarting time
Table 12:Minimum reactance (40)
Features:
- Detection of loss-of-excitation failure of synchronous machines- Single- or three-phase measurement
- Out-of-step detection with additional time delay or count logic- Circular characteristic
- Tripping possible inside or outside the circle
Fig. 4Settings:
Minimum reactance protection function characteristics
-5 to 0 UN/lN in steps of 0.01 UN/lN-2.5 to + 2.5 UN/lN in steps of 0.01 UN/lN0.2 to 60 s in steps of 0.01 s-180° to +180° in steps of 5°
Reactance XAReactance XBDelayAngle
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 13
Accuracy of pick-up valuesReset ratio
± 5% of highest absolute value of XA, XB (at fN)(related to origin of circle),105% for min. function. 95% for max. function.≤ 80 ms
Starting time
Table 13:Power (32)
Features:Applicable for
- Active power protection- Reverse power protection- Reactive power protection
- Maximum and minimum function
- Single- or two- or three-phase measurement
- Adjustable compensation angle for input transformer errorsSettings:Power
Minimum setting:AngleDelay
Compensation angleNominal power PNReset ratioAccuracy
-0.1 to 1.2 PN in steps of 0.005 PN- 0.005 PN (with measuring CT)- 0.02 PN (with protection CT)-180° to +180° in steps of 5°0.05 to 60s in steps of 0.01 s-5° to +5° in steps of 0.l°
0.5 to 2.5 UN · IN in steps of 0.001 UN . IN30% to 170% in steps of 1%
± 0.5% PN (at fN, I < IN) with measuring CTs
Table 14:Stator overload (49S)
Features:
- Single- or three-phase measurement
- Operating characteristics according to ASA-C50.13 - Highest phase value for three-phase measurement- Wide time multiplier setting.
Fig. 5Settings:
Stator overload protection function characteristics
0.5 to 2.5 IN in steps of 0.01 IN1 to 50 s in steps of 0.1 s1.0 to 1.6 IB in steps of 0.01 IB
Base current (IB)Time multiplier k1Pick-up current (Istart)
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 14
Technical data (cont´d)
tmintgtmaxtreset
Accuracy of current measurementStarting time
1 to 120 s in steps of 0.1 s10 to 2000 s in steps of 10 s100 to 2000 s in steps of 10 s10 to 2000 s in steps of 10 s
± 5% (at fN), ± 2% (at fN) with measuring transformer≤ 80 ms
Table 15:Rotor overload (49R)
Features:
Same as stator overload function, but three-phase measurementSettings:
Same as for stator overload function
Table 16:Inverse time negative phase sequence current (46)
Features:
- Protection against unbalanced load- Inverse time delay
- Three-phase measurement
Fig. 6
Inverse time negative phase
sequence current protection function characteristics
0.5 to 2.5 IN in steps of 0.01 IN5 to 30 s in steps of 0.1 s0.02 to 0.20 in steps of 0.011 to 120 s in steps of 0.1 s500 to 2000 s in steps of 1 s5 to 2000 s in steps of 1 s
+2% (at fN) with measuring transformers≤ 80 ms
Settings:Base current (IB)Time multiplier k1Factor k2 (pick-up)tmintmaxtreset
Accuracy of NPS current (I2) measurementStarting time
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 15
Table 17:Overtemperature (49)
Features:
- Thermal replica for system of first order or general thermal system response- Single- or three-phase current measurement
- Highest phase value for three-phase measurementSettings:Base current IBWarning stageTripping stageThermal time constant
Accuracy of current measurementAccuracy of the thermal image
0.5...2.5IN in steps of 0.01IN50...200% ϑN in steps of 1% ϑN50...200% ϑN in steps of 1% ϑN0.0...500min in steps of 0.1min± 2% (at fN) with measuring transformers±5%
Table 18:Frequency (81)
Features:
- Maximum or minimum function (over-, underfrequency)- Minimum voltage blockingSettings:FrequencyDelay
Minimum voltageAccuracy of pick-up valueReset ratioStarting time
40 to 65 Hz in steps of 0.01 Hz0.1 to 60 s in steps of 0.01 s0.2 to 0.8 UN in steps of 0.1 UN± 30 mHz (at UN and fN)< 106%< 135 ms
Table 19:df/dt (81)
Features:
- combinde pick-up with frequency criterion possible- blocking by undervoltageSettings:df/dtFrequencyDelay
Minimum voltageAccuracy of df/dtAccuracy of frequencyReset ratio df/dt
-10 to +10 Hz/s in steps of 0.1 Hz/s40 to 65 Hz in steps of 0.01 Hz0.1 to 60 s in steps of 0.01 s0.2 to 0.8 UN in steps of 0.1 UN± 0.1 Hz/s
± 30 mHz (at UN and fN)95% for max. function105% for min. function
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 16
Technical data (cont´d)
Table 20:Overexcitation (24)
Features:
- U/f measurement
- Minimum voltage blockingSettings:Pick-up valueDelay
Frequency rangeAccuracyReset ratioStarting time
0.2 to 2 UN/fN in steps of 0.01 UN/fN0.1 to 60 s in steps of 0.01 s0.5 to 1.2 fN± 3% (at fN)
> 97% (max.), < 103% (min.)≤ 120 ms
Table 21:Overexcitation function with inverse time delay (24)
Features:
-Single-phase measurement-inverse time delay
-According to IEEE Guide C37.91-1985 setting made by help of table settings Settings:Table settingsStart value U/ftmintmaxReset timeReference voltageAccuracy of pick-up valueFrequency rangeReset ratioStarting time
U/f values: (1.05; 1.10 to 1.50) UN/fN1.05 to 1.20 UN/fN in steps of 0.01 UN/fN0.01 to 2 min in steps of 0.01 min5 to 100 min in steps of 0.1 min0.2 to 100 min in steps of 0.1 min0.8 to 1.2 UN in steps of 0.01 UN± 3% UN/fN (at fN)0.5 to 1.2 fN100%> 120 ms
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 17
Table 22:Voltage balance function (60)
Features:
-Comparing of the voltage amplitudes of two groups of voltage inputs (line 1, line 2)-1- or 3-phase voltage measurement
-Signalling of the group having the lower voltage
-Evaluation of the voltage differences per phase for the 3-phase function and logic OR connection for the tripping decision
- Variable tripping and reset delay-Suppression of d. c. components-Suppression of harmonics
Fig. 7Settings:
Tripping characteristic Voltage comparison (shown for the phases R and the setting value volt. diff. = 0.2 . UN)
0.1 to 0.5 UN in steps of 0.05 UN0.00 to 1.0 s in steps of 0.01 s0.1 to 2.0 s in steps of 0.01 s1 or 3≤ 50 ms
phase R voltage amplitude voltage channel 1 (line 1)phase R voltage amplitude voltage channel 2 (line 2)
Voltage differenceTrip delayReset delayNumbers of phases
Maximum tripping time without delayU1R:U2R:
For 3-phase function: the characteristic is valid accordingly for the phases S and T
Table 23:Dead machine protection (51, 27)
Features:
-Quick separation from network at accidental energization of generator (e.g. at standstill or on turning gear)
-Instant overcurrent measurement
-Voltage-controlled overcurrent function e.g. blocked at voltage values > 0.85 UN
This function does not exist in the library, it must be combined from the voltage current and time function Settings:VoltageReset delayCurrentDelay
0.01 to 2 UN in steps of 0.002 UN0 to 60 s in steps of 0.01 s0.02 to 20 IN in steps of 0.02 IN0.02 to 60 s in steps of 0.01 s
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 18
Technical data (cont´d)
Table 24:100% Stator earth fault protection (S)
Features:
-Protection of the entire stator winding, including star points, even at standstill. Works also for most of theoperating conditions.
- Also suitable when 2 earthings (groundings) are in the protection zone-Continuous supervision of the insulation level of the stator
-Based on the earth (ground) voltage displacement principle and calculation of the earth (ground) fault resistance
-Alarm and tripping values are entered, resp. measured and displayed in kΩ-Type of earthings (groundings):
-star point earthing with resistors (requires REX011)
-star point earthing with grounding transformer (requires REX011-1)-earthing transformers on generator terminals (requires REX011-2)Settings:Alarm stageDelayTripping stageDelayRES
Number of star pointsRES-2. starpointReset ratioAccuracyStarting time
Functional requirements:- max. earthing current- stator earthing capacity- stator earthing resistance RPS- stator earthing resistance RES
(All values are based on the starpoint side)
The actual earthing resistances RES + RPS have to be calculated in accordance with the User’s Guide:The 100% stator earth fault protection function always requires an injection unit type REX010, an injection transformer block type REX011 and a 95% stator earth fault protection function.
I0 < 20A (recommended I0 = 5A)0.5 µF to 6 µF130Ω to 500Ω
700Ω to 5 kΩ (≥4.5 x RPS)100Ω to 20 kΩ0.2 s to 60 s100Ω to 20 kΩ0.2 s to 60 s700Ω to 5 kΩ2
900Ω to 30 kΩ
110% for setting values of ≤ 10 kΩ120% for setting values of > 10 kΩ0.1 kΩ to 10 kΩ: < ± 10%
0 to 100 Ω, 10 kΩ to 20 kΩ: < ± 20%1.5 s
Table 25:Rotor earth fault protection (R)
Features:
-Continuous supervision of the insulation level and calculation of the earthing (grounding) resistance-Alarm and tripping values are entered resp. measured and displayed in kΩSettings:Alarm stageDelayTripping stageDelayRER
Coupling capacityReset ratio
100Ω to 25 kΩ0.2 s to 60 s100Ω to 25 kΩ0.2 s to 60 s900Ω to 5 kΩ2 µF to 10 µF110%
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 19
AccuracyStarting time
Functional requirements:- total rotor earthing capacity- rotor earthing resistance RPR- rotor earthing resistance RER- coupling capacity- time constant
0.1 kΩ to 10 kΩ < ±10%
0 to 100 Ω, 10 kΩ to 25 kΩ < ±20%1.5 s
200 nF to 1µF100 Ω to 500 Ω900 Ω to 5 kΩ4 µF to 10 µ F
T = RER, x C = 3 to 10 ms
The actual earthing resistance RER + RPR have to be calculated in accordance with the User’s Guide. The 100% rotor earth fault protection function always requires an injection unit type REX010 and an injec-tion transformer block type REX011 which are connected to the plant via coupling capacities.
Table 26:Pole slip protection (78)
Features:
-Recording the pole wheel movements from 0.2 Hz to 8 Hz
-Differentiation of the pendulum center inside or outside of the generator-transformer block zone by two independent tripping stages
-Adjustable warning angle for pole wheel movements-Number of slips adjustable before tripping
Fig. 8Settings:
Characteristic of the function
0 to 5.0 UN/lN-5.0 to 0 UN/lN0 to 5.0 UN/lN60° to 270°0° to 180°0° to 180°0 to 200 to 200.5 s to 25 s
ZA (system impedance)ZB (generator impedance)ZC (impedance step 1)Phi
warning angletripping anglen1n2t-reset
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 20
Technical data (cont´d)Table 27:Synchrocheck (25)
Features:
-Supervision of synchronism.
Single-phase measurement. The differences of the amplitudes, phase angles and frequencies of two voltage-vectors are checked-Voltage supervision:
Single- or three-phase voltage measurement. Evaluation of instantaneous values and therefore a large frequency range. Detection of maximum and minimum values in case of three-phase input-Phase-selection of the voltage-inputs
-External switch over to another voltage input is possible (for double busbar systems)-External selection of the modeSettings:Max. voltage diff.Max. phase diff.Max. frequency diff.Min. voltageMax. voltageSupervision timeReset time
0.05 to 0.4 UN in steps of 0.05 UN5 to 80 deg in steps of 5.0 deg0.05 to 0.4 Hz in steps of 0.05 Hz0.6 to 1 UN in steps of 0.05 UN0.1 to 1 UN in steps of 0.05 UN0.05 to 5 s in steps of 0.05 s0 to 1 s in steps of 0.05 s
Table 28:Metering functions U, I, P, Q, f
SettingVoltage UNCurrent INReal power PApparent power Q
Range0 to 1.2 UN0 to 20 IN0 to 1.2 UN0 to 20 IN0 to 1.2 UN0 to 20 IN
Accuracy0.5%2%
1% resp. 0.5%*3% resp. 2%*2% resp.0.5%*5% resp. 3%*2% resp. 0.5%*5% resp. 3%*
Minimum
0.002 UN (compensated)0.005 UN (uncompensated)0.01 IN (compensated)0.02 IN (uncompensated)0.02 PN (compensated)0.05 PN (uncompensated)0.02 PN (compensated)0.05 PN (uncompensated)
* applies for toroidal core c.t’s (0 to 2 IN)Table 29:Disturbance recorder
Max. 12 analogue channelsMax. 16 binary channels
Max. 12 analogue channels of internal measurement values
12 samples per period (sampling frequency 600 or 720Hz at a rated frequency of 50/60Hz)Available recording time for 9 analogue and 8 binary signals approximately 5sRecording initiated by any binary signal, e.g. the general trip signal.Data formatDynamic rangeResolutionSettings:
Recording periods
Pre-event Event
Post-event
40...400ms in steps of 20ms100...3000ms in steps of 50ms40...400ms in steps of 20msEVE
70 x IN, 2.2 x UN12 bits
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 21
Table 30:Logic functions
Delay function:
- Adjustable trip delay and drop delay- Two time integration modes- Input invertible
Counting function:
- Adjustable trip counting threshold and drop delay- Input invertible
AND function
- Maximum of four inputs- All inputs invertible
- Trip with additional delay or counting functionOR-function
- Maximum of four inputs- All inputs invertible
- Trip with additional delay or counting functionFLIP-FLOP function
- Two set- and two reset inputs- All inputs invertible
- Trip with additional delay or counting function
0 to 300 s in steps of 0.01 s
1 to 100 in steps of 1
Table 31:Configuration and Settings
Locally via the comm. port on the front-plate using an IBM AT or compatible PC
User interface program in English, German, French or Spanish on a disc (31/2\"/1.44 MByte or 51/4\"/1.2 MByte)
Table 32:Remote communication
RS232C interface
Data transfer rateProtocol
Electrical/optical converter (optional)PC-Card interface
Number
PC-Cards (optional)
for interbay busfor process bus
(interbay and process bus can be used concurrently)LON bus
Data transfer rateIEC 1375 busData transfer rateEvent memory
Capacity
Time marker resolutionEngineering interface
9 pin Sub-D female9600 Bit/s
SPA or IEC 870-5-103216BM61b
2 plug-in sockets for type 3 cardsLON or IEC 1375 protocolIEC 1375 protocol
PC-Card with fibre-optical port, ST connectors1.25 MBit/s
PC-Card with redundant fibre-optical port, ST connectors1.5 Mbit/s256 events1 ms
integrated software interface for signal engineering with SigTOOL
Table 33:Contact data
Tripping:
Max. operating voltageMake and carry for 0.5 sContinuous currentMaking power
250 VAC or VDC30 AAC or A DC10 AC or A DC2500 VA
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 22
Technical data (cont´d)
Rupture current with two contacts in series andL/R = 40 ms
at U ≤ 50 VDCat U ≤ 120 VDCat U ≤ 250 VDCSignalling stand by
No. of contacts (216GA61)No. of contacts (216GD61)Max. operating voltageMake and carry for 0.5 sContinuous currentMaking power
5 A1 A0,3 A
2 break contacts per signalling channel1 make contact per signalling channel4 signalling channels with 1 break contact250VAC or VDC10 AAC or ADC5 AAC or ADC1250 VAAC 60 WDC
Table 34:Auxiliary supply
Max. installed rating per cubicleSupply interruption bridging time
at min input voltage and full loadat rated input voltage and 70% load
400W> 10 ms> 50 ms
Table 35:General data
Temperature range
operationstorageHumiditySeismic testInsulation test
-10° C...+55°C-40°C...+85°C93%, 40°C, 4 days5g, 30s, 1..33Hz (1 octave/min)
2kV, 50Hz, 1 min
1kV across open contacts
0.5kV at the serial interface on the front-plate
>100MΩ, 500VDC5kV, 1.2/50µs1.0/2.5 kV, Cl. 3; 1MHz,400 Hz rep.freq.2/4 kV, Cl. 4
6/8 kV (10 shots), Cl. 31000 A/m 50/60 Hzpermanent field
• 0.15-80 MHz, 80% amplitude modulated10 V, cl. 3
• 80-1000 MHz, 80% amplitude modulated10 V/m, cl. 3
• 900 MHz, puls modulated10 V/m, cl. 3Cl. A
IEC 255-6 (1988)IEC 68-2-3 (1984)IEC 255-21-3 (1993)IEEE 344 (1987)IEC 255-5 (1977)
Leakage resistanceSurge voltage test
1 MHz burst disturbance test
IEC 255-5 (1977)IEC 255-5 (1977)IEC 255-22-1 (1988)ANSI/IEEE C37.90.1 (19)
EN61000-4-4 (1994), IEC 1000-4-4 (1995)EN 61000-4-2 (1994),IEC 1000-4-2 (1995)EN 61000-4-8 (1993),IEC 1000-4-8 (1993)ENV50141 (1993)ENV 50140 (1995),IEC 1000-4-3 (1995)ENV 50204 (1995)EN 50081-2 (1994),(EN55011 (1992),CISPR 11 (1990)),(EN 55022 (1995), CISPR 22 (1995))
Fast transient test
Electrostatic discharge test (ESD)
Immunity to magnetic interfer-ence at power system frequen-cies
Radio frequency interference test (RFI)
Emission
* Reduced values apply for repeat tests according to IEC publication 255-5, Clauses 6.6 and 8.6.
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 23
Table 36:Mechanical design
Terminals
CT and PT circuits
tripping and signalling circuits
aux. dc supply and remaining aux. circuitsCubicle wiringCT and PT circuitsaux. dc supply
tripping and signalling circuitsstandard pre-made cablesCubicle design
Cubicle dimensions (w x d x h)
Total weight (with all aux. relays and units inserted)
10 mm2, Type Phoenix URTK/S4 mm2, Type Phoenix UKK5-MT KD-P/P(GKOS for 216GD61)
10 mm2, Type Phoenix UK4 (GKOS for 216GD61)directly mounted terminals1.50 mm20.5 mm20.25 mm2
ABB Type RESP (see catalogue 1MDB14004-EN)800 x 800 x 2200 mm200 to 400 kg
Ordering
In order to configure the generator protection system type REG216 the ABB-engineering group needs the information from the Ques-tionnaire 1MRB520026-Ken.
When ordering the compact version the fol-lowing has to be stated: •Rated current•Rated voltage•Optocoupler voltage
•Quantity of different units (electronic part) and interfaces
Table 37:Subcodes
SubcodeA-A0A1A2A5B0B1B2B5U0U1U2K01L01
Explanationnone1A2A5Anone1A2A5A
none
100...130VAC200...230VAC6 CT’s (3ph1 MT (1ph2 VT (1ph
3 VT (3ph delta6 CT’s (3ph3 MT’s (3ph
3 VT’s (3ph delta
1) 216GW62 Input transformer assembly2) 216GD61 Interface unit consisting of:8 tripping relays16 signalling relays16 optocouplers3 cables 216IK61
NOTE:
The compact version in addition requires con-figuration and final testing, which is normally not included. For customizing the compact version, please contact an ABB Power Auto-mation sales representative.
Descriptionrated current
Remarks for orderingfor protection transf.
B-rated currentfor measurement transf.
U-rated voltage
K-/L-
Code A-)Code B-)Code U-)Code U-)Code A-)Code B-)Code U-)
VT,CT and MTarrangement of transformer unit
Typ 216GW62Explanation:
CT= Protection transformerVT= Voltage transformer
MT= measurement transformer
K02L02
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 24
Ordering (cont´d)
K03L03K04L04
6 CT’s (3ph
3 VT’s (3ph delta3 VT’s (3ph delta6 CT’s (3ph1 CT (1ph1Mt (1ph1 VT (1ph
3 VT (3ph delta9 CT’s (3ph1 MT (1ph2 VT’s (1ph9 CT’s (3ph
3 VT’s (3ph delta12 CT’s (3ph9 CT’s (3ph 3 MT’s (3ph3 CT’s (3ph3 MT’s (3ph
3 VT’s (3ph delta2 VT’s (1ph1 MT (1ph6 CT’s (3ph
3 VT’s (3ph delta3 VT’s (1ph 9 CT’s (3ph3 VT’s (3ph star3 CT’s (3ph
3 VT’s (3ph delta1 VT (1ph1 MT (1ph1 VT (1ph3 VT’s (spez.6 CT’s (3ph
3 VT’s (3ph delta1 VT (1ph2 VT’s (spez.1*GW621*GD61a
Code A-)Code U-)Code U-)Code A-)Code A-)Code B-)Code U-)Code U-)Code A-)Code B-)Code U-)Code A-)Code U-)Code A-)Code A-)Code B-)Code A-)Code B-)Code U-)Code U-)Code B-)Code A-)Code U-)Code U-)Code A-)Code U-)Code A-)Code U-)Code U-)Code B-)Code U-)Code U-)Code A-)Code U-)Code U-)Code U-)Code K-Code I-Code K-/ L-Code I-/J-Code K-/ L-Code I-/J-Code K-Code I-/J- Code K-Code I-/J-The variants M2,M3, M6 and M7 con-sisting of two units GW62. The first is specified with code Kx- and the second with code Lx-
K05L05K06L06K07L07K08L08K09L09
K10L10K11L11K12L12
95% Stator earth fault protection
100% Stator- + rotor earth fault protec-tion
K13L13
95% Stator earth fault protection100% Stator earth fault protection
M-M11*rack 216MB66 consisting of 1*NG6x, 1*EA61b, 1*AB61, 1*DB61
M21*rack 216MB66 consisting of 1*NG6x, 1*EA61b, 1*AB61, 2*DB612*GW622*GD61a
M31*rack 216MB66 consisting of 1*NG6x, 1*EA61b, 1*AB61, 1*DB612*GW621*GD61a
M41*rack 216MB66 consisting of 1*NG6x, 1*EA61b, 1*AB61, 2*DB611*GW622*GD61a
M51*rack 216MB68 consisting of 1*NG6x, 1*EA61b, 1*AB61, 1*DB61 per group1*GW622*GD61a
M61*rack 216MB68 consisting of 1*NG6x, 1*EA61b, 1*AB61, 1*DB61 per group
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 25
2*GW622*GD61a
M7
2*GW624*GD61a
Code K- / L-Code I-/J-Code K- / L-Code I-/J-
1*rack 216MB68 consisting of 1*NG6x, 1*EA61b, 1*AB61, 2*DB61 per group
The above mentioned devices are included in the code Mx. The number and types of CPU’s must be specified by code
G-G1G2G4H1H2H4I0I1I2I3S1S2S3S4T0T6V5
165...312 V DC82.....156 V DC36......75 V DC165...312 V DC82.....156 V DC36......75 V DCnone
82...312 V DC36....75 V DC20....30 V DCSPA protocolLON protocolMVB protocolnone
Lithium-battery216VC62a
(S3/S4 only valid for new CPU 216VC62a)(Interbay- or/and process bus)
(216VC62a includes gold capacitor, no battery)(T-code for new CPU not necessary)425%
1.CPU
Communication and Dist.recorder included
Communication and Dist.recorder includedReset unit
Diskette for user interface program.
1.DC/DC-con-verter supply voltage2.DC/DC-con-verter supply voltage
for variant M1-M4 an optional 2. redun-dant DC/DC-converter can be used
H-
I-
Binary input/output unit GD61aoptocoupler input voltage
S-
T-V-
W-R-P-
W5R0R1PDPEPF
216VC62anoneavailable
German 3½“ (1.44MB)English 3½“ (1.44MB)French 3½“ (1.44MB)
425%
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 26
Ordering (cont´d)
Table 38:Accessories
PCC card interfaceType
For interbay bus:PCCLON2 SET500PCC02For process bus:500PCC02Type216BM61b
ProtocolLONIEC 1375IEC 1375
ConnectorST (bajonet)ST (bajonet)ST (bajonet)
Optical fibre*G/GG/GG/G
Gauge **62,5/12562,5/12562,5/125
ID No
HESG 448766R0001HESG 448735R0231HESG 448735R0232
RS232C interbay bus interface
ProtocolSPA
ConnectorST (bajonet)
Optical fibre*G/G
Gauge **62,5/125
Order No.
Type/ID No.HESG448267R1021
* receiver Rx / transmitter Tx, G = glass, P = plastic Operator program disk (DOS-based)Language
German/English/French
Disk 3½“ (1.44MB)
**optical fibre conductor gauge in µm
Order No.Type/ID No.HESG448753R1
* Unless expressly specified the latest version is supplied.Operator program disk (Windows-based)LanguageEnglish
Optical fibre PC connecting cableType
YX216a-1 (4 m)YX216a-1 (10 m)YX216a-1 (30 m)
Disturbance recorder evaluation programType, descriptionREVAL EnglishREVAL GermanWINEVEWINEVE
3½“-Disk3½“-DiskEnglish/GermanEnglish/German
Order No.1MRK000078-A1MRK000078-D
Basic versionFull versionType/ID No.
Order No.7433 10-AA7433 10-BA7433 10-CA
Type/ID No.HESG448522R1HESG448522R2HESG448522R3
DiskCD ROM
Order No.
Type/ID No.HESG448798R0001
* Unless expressly specified the latest version is supplied.
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 27
Variant M1 (single system)
Standard configuration:- 1*216NG6x- 1*216VC62a- 1*216EA61b- 1*216AB61- 1*216DB61
- 12 Input transformers- 8 Tripping relays - 16 Signalling relays - 16 Binary inputs Code G
(1*GW62)(1*GD61a)( „ )( „ )Code K
Code IOption:- additional CPU type 216VC62a - 2. DC/DC-converter (for redundant power supply)Ordering example for Racks with CPU-type 216VC62aHESG 324510 M1Code: M1K*A*B*U*G*H*I*V5W*S*R* P*3ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 28
Ordering (cont´d)Variant M2 (single system)
Standard configuration:- 1*216NG6x- 1*216VC62a - 1*216EA61b- 1*216AB61- 2*216DB61
- 24 Input transformers- 16 Tripping relays - 32 Signalling relays - 32 Binary inputs Code G
(2*GW62)(2*GD61a)( „ )( „ )Code K / L
Code IOption:- additional CPU type 216VC62a - 2. DC/DC-converter (for redundant power supply)Ordering example for Racks with CPU-type 216VC62aHESG 324510 M1Code: M2K*L*A*B*U*G*H*I*V5W*S*R*P*3ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 29
Variant M3 (single System)
Standard configuration:- 1*216NG6x- 1*216VC62a - 1*216EA61b- 1*216AB61- 1*216DB61
- 24 Input transformers- 8 Tripping relays - 16 Signalling relays - 16 Binary inputs Code G
(2*GW62)(1*GD61a)( „ )( „ )Code K / L
Code IOption:- additional CPU type 216VC62a - 2. DC/DC-converter (for redundant power supply)Ordering example for Racks with CPU-type 216VC62aHESG 324510 M1Code: M3K*L*A*B*U*G*H*I*V5W*S*R*P*3ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 30
Ordering (cont´d)Variant M4 (single System)
Standard configuration:- 1*216NG6x- 1*216VC62a- 1*216EA61b- 1*216AB61- 2*216DB61
- 12 Input transformers- 16 Tripping relays - 32 Signalling relays - 32 Binary inputs Code G
(1*GW62)(2*GD61a)( „ )( „ )Code K
Code IOption:- additional CPU type 216VC62a - 2. DC/DC-converter (for redundant power supply)Ordering example for Racks with CPU-type 216VC62aHESG 324510 M1Code: M4K*A*B*U*G*H*I*V5W*S*R* P*3ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 31
Variant M5 (redundant System)
Standard configuration:- 1*216NG6x (per group)- 1*216VC62a (per group)- 1*216EA61b (per group)- 1*216AB61 (per group)- 1*216DB61 (per group)- 12 Input transformers- 8 Tripping relays - 16 Signalling relays - 16 Binary inputs Option:- noneCode G
(1*GW62)(1*GD61a)( „ ) ( „ ) Code K / L(per group)(per group)(per group)Ordering example for Racks with CPU-type 216VC62aHESG 324510 M1Code: M5K*A*B*U*G*H0 I*V5W5S*R* P*3ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 32
Ordering (cont´d)Variant M6 (redundant system)
Standard configuration:- 1*216NG6x (per group)- 1*216VC62a (per group)- 1*216EA61b (per group)- 1*216AB61 (per group)- 1*216DB61 (per group)- 24 Input transformers- 8 Tripping relays- 16 Signalling relays- 16 Binary inputsOption:- noneCode G
(2*GW62)(1*GD61a)( „ )( „ )Code K / L(per group)(per group)(per group)Ordering example for Racks with CPU-type 216VC62aHESG 324510 M1Code: M6K*L*A*B*U*G*H0 I*V5W5S*R*P*3ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 33
Variant M7 (redundant System)
Standard configuration:- 1*216NG6x (per group)- 1*216VC62a (per group)- 1*216EA61b (per group)- 1*216AB61 (per group)- 2*216DB61 (per group)- 24 Input transformers- 16 Tripping relays- 32 Signalling relays- 32 Binary inputsOption:- none Code G
(2*GW62)(2*GD61a)( „ )( „ )Code K / L(per group)(per group)(per group)Ordering example for Racks with CPU-type 216VC62aHESG 324510 M1Code: M7K*L*A*B*U*G*H0 I*V5W5S*R*P*3Accessories (optional)ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 34
Accessories (optional)
This may also be obtained elsewhere, how-ever correct operation of the overall system is crucial.
Printer to be connected to the PC.
EPSON type FX800 must possess a parallel Centronics interface.
Personal computer
event that the software functions increase (graphic display, etc.). Following require-ments should be met:
MByte RAM
Disk drive 3.5\1 CD-ROM drive
1 Hard disk minimum 500 MB1 serial interface (RS 232 C)2nd serial interface as option
A monochrome screen controller able to show block graphics (800 x 600 points or bet-ter)
•duplicating the whole system
Additional benefits considered are wide set-ting ranges, excellent long-term stability and few setting steps. The numerical system should offer a library of the available protec-tive functions. These functions will then be selected by the user by the simple assignment of parameters.
All protection functions should operate from sampled primary system voltages and cur-rents. The sampling rate of the analogue input units should be 12 times per period at rated power system frequency with a dynamic range of 15 bit.
The man-machine-communication should be performed easily using only a few push-but-ton commands on a personal computer (PC) via a serial RS 232 interface. No prior knowl-edge of programming should be necessary. For all functions the user is guided with the aid of screen menus and windows. All differ-ent languages for texts could be supplied. Any text change is accommodated easily.All the hardware components should be pack-aged in a single cabinet. This cubicle can also accommodate other protection relays with external functions, for example, 100% stator earth fault protection, Buchholz relay or some thermal sensors.
Various PC’s having a RS232 and working with the operating systems, Windows 95 or Windows NT 4.0 can be used. This PC type can also be used in the future in the probable
Sample
specification
Numerical protection equipment used for generator and block-transformer protection. It will be a stand-alone system but closely involved in the process. Parameters, signals, measured values as well as remote parameter regulation commands, will be exchanged via appropriate interfaces and a serial communi-cations channel to central process control equipment.
The system will be supported by a software library of diverse protection functions. A menu-driven HMI (human machine interface) will allow users to activate functions which are provided in the protection function library.The entire protective system will consist of a relatively small number of hardware compo-nents. This applies not only to the electronic units, but also to the process interfaces, such as current and voltage inputs as well as the numbers of signal and tripping relays.This flexibility resulting from the modular hardware will enable the equipment configu-ration to be easily adapted for installations of different sizes and the desired scope of pro-tection.
The system will permit various degrees of redundancy. The user can specify the desiredconfiguration
•duplicating power supply unit
ABB Power Automation
Numerical generator protection
REG216/ REG216
Compact
1MRB520004-Ben
Page 35
References
Relay mounting systemsOperating Instructions
REG 216 Numerical Generator Protection SystemQuestionnaire REG 216Reference List
1 MDB14004-EN1 MDU02005-EN1MRB520026-Ken1MRB520011-Ren
ABB Power Automation
Numerical generator protection
ABB Power Automation AG
Haselstrasse 16/122
CH-01 Baden/SwitzerlandTel. +41 56 205 77 44Fax +41 56 205 55 77Homepage:www.abb.ch/chpauPrinted in Switzerland (9911-1500-0)
REG216/ REG216
Compact
1MRB520004-Ben
Page 36
因篇幅问题不能全部显示,请点此查看更多更全内容
Copyright © 2019- huatuo0.com 版权所有 湘ICP备2023021991号-1
违法及侵权请联系:TEL:199 1889 7713 E-MAIL:2724546146@qq.com
本站由北京市万商天勤律师事务所王兴未律师提供法律服务