您好,欢迎来到华佗健康网。
搜索
您的当前位置:首页ABB变频器、变流器和逆变器选项 FDCO-01 02 DDCS通信模块用户手册

ABB变频器、变流器和逆变器选项 FDCO-01 02 DDCS通信模块用户手册

来源:华佗健康网
—

OPTIONS FOR ABB DRIVES, CONVERTERS AND INVERTERS

FDCO-01/02 DDCS communication modules

User’s manual

List of related manuals

*Lists of hyperlinks to product manualsACS880-01ACS880-04

ACS880-07 (45 to 710 kW)ACS880-07 (560 to 2800 kW) ACS880-07CLC drivesACS880-07LC drivesACS880-11 drives

ACS880-14 drive modulesACS880-17 (45 to 400 kW)ACS880-17 (160 to 3200 kW)ACS880-17LC drivesACS880-31 drives

ACS880-34 drive modulesACS880-37 (45 to 400 kW)ACS880-37 (160 to 3200 kW)ACS880-37LC drivesACS880 multidrives

ACS880 multidrive modules

Code

9AKK1008A70049AKK105713A48199AKK1008A81499AKK105713A66639AKK107046A02399AKK107680A92759AKK106930A95659AKK107045A80239AKK106930A34669AKK1063A14999AKK107492A47219AKK106930A959AKK107045A80259AKK106930A34679AKK1063A15009AKK107492A47229AKK106103A91229AKK105713A3673

Option manuals and guides

FDCO-01/02 DDCS communication modules 3AUA0000114058user’s manual

You can find manuals and other product documents in PDF format on the Internet. See section Document library on the Internet on the inside of the back cover. For manuals not available in the Document library, contact your local ABB representative.

*Available in the Document library

3

Table of contents

1. FDCO-01/02 DDCS communication modules

Introduction to the manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Safety in installation and maintenance . . . . . . . . . . . . . . . . . 5Target audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Terms and abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Hardware description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7Mechanical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

Unpacking and checking the delivery . . . . . . . . . . . . . . . . . . .7Installing the module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8Electrical installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Dimension drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Degree of protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Ambient conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Operating voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11Current consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

Further information

4

FDCO-01/02 DDCS communication modules 5FDCO-01/02 DDCS

communication modules

Introduction to the manual

Safety in installation and maintenance

These instructions are for all who install or connect an optional module to a drive, converter or inverter and need to open its front cover or door to do the work.

WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the equipment can occur.

••

If you are not a qualified electrician, do not do installation or maintenance work.

Disconnect the drive, converter or inverter from all

possible power sources. After you have disconnected the drive, converter or inverter, always wait for 5 minutes to let the intermediate circuit capacitors discharge before you continue.

Disconnect all dangerous voltages connected to other control signal connectors in reach. For example, it is

possible that 230 V AC is connected from outside to a relay output of the drive, converter or inverter.

Use a voltage tester to measure that there are no live parts within reach.

6 FDCO-01/02 DDCS communication modules Target audience

This manual is intended for people who plan the installation, install, start up, use and service the communication module. Before you do work on the module, read this manual and the applicable drive, converter or inverter manual that contains the hardware and safety instructions for the product in question.

You are expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols.

The manual is written for readers worldwide. Both SI and imperial units are shown.

Terms and abbreviations

Later in this manual, term drive substitutes for string drive/converter/inverter.

Hardware description

The FDCO DDCS communication module enables fiber optic connection on the DDCS protocol for ABB drives. The module includes the connectors for fiber optic DDCS channels Ch A and Ch B (see 1 and 2 below) and selectors for both channels to make sure that the transmitter current is optimal for the cable length (see 3 and 4 below).

The module makes the signal and power connection to the drive through a 20-pin connector.

FDCO-01/02 DDCS communication modules 7Layout

Item5124334567DescriptionConnector for Ch AConnector for Ch BSelector for Ch ASelector for Ch BLockMounting screw7 LEDs612Mechanical installation

Unpacking and checking the delivery

1.

Open the package.

2.Make sure that the package contains:

FDCO-01/02 moduleThis manual.

3.Make sure that there are no signs of damage.

8 FDCO-01/02 DDCS communication modules Installing the module

WARNING! Obey the safety instructions. If you ignore the safety instructions, injury or death can occur.

See the drive hardware manual for the position of the module in the drive. Plastic pins, a lock and one screw hold the module in place. The screw also makes an electrical connection between the module and drive frame for cable shield termination.

To install or remove the module from the control unit:1.

Pull out the lock.

2.Put the module carefully into its position on the drive.3.Push in the lock.

4.Tighten the screw to 0.8 N·m (7 lbf·in).

Note: It is necessary to tighten the screw correctly to fulfill the EMC requirements and to ensure the correct operation of the module.134FDCO-01/02 DDCS communication modules 9Electrical installation

Notes:

•••

1.

Transmitter and receiver have to be of the same type at both ends of the link.

Observe color coding and terminal markings so that transmitters are connected to receivers and vice versa.If multiple devices are to be connected to one channel, connect them in a ring.

Lead the fiber optic cables from the external device to the appropriate channel(s) of the FDCO-01/02.

2.Inside the drive, route the cables as shown in its hardware

manual. Make sure the cables are not kinked or laid against sharp edges.3.Select switch positions for both channels to match the

cable lengths according to the following table.

Using a transmitter current that is higher than

recommended reduces LED lifetime and increases power consumption and heat generation.

Switch position0 - OFF1 - SHORT2 - MEDIUM3 - LONG

Transmitter current0 mA30 mA40 mA50 mA

Cable lengthPOF, 1mmDisabled0.1 … 20 m20…25 m25…30 m

0.1 … 50 m50…100 m100…200 mHCS, 200 µm *

* HCS cannot be used with FDCO-02 channel A.

10 FDCO-01/02 DDCS communication modules Diagnostics

LEDs

LabelPWR OKCh A Rx/TxCh B Rx/TxColorGreenGreen/RedGreen/RedDescriptionPower / Internal 3.3 V OKDDCS channel A data activityDDCS channel B data activityTechnical dataDimension drawingFDCO-01/02 DDCS communication modules 11Installation

Into an option slot on the drive control unit

Degree of protection

IP20

Ambient conditions

The applicable ambient conditions specified for the drive in its hardware manual are in effect.

Package

Cardboard. Plastic wrapping: Antistatic air bubble sheet (PE).

Connectors

•••

20-pin F-series module connector

2 transmitter/receiver connector pairs for fiber optic cablesBaud rates:

Channel A (Ch A)10 MBd5 MBd

Channel B (Ch B)10 MBd10 MBd

Module typeFDCO-01FDCO-02

Operating voltage

3.3 V DC (supplied by the drive control unit)

Current consumption

300 mA max

12 FDCO-01/02 DDCS communication modules General

Complies with standards IEC 61800-3, IEC 61000-4-4, IEC61000-4-5, IEC 61000-4-6, IEC 61000-4-2, IEC61000-4-3, RoHS

Printed circuit board conformal coated Printed circuit board materials UL Recognized

••

Further information

Product and service inquiries

Address any inquiries about the product to your local ABB

representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to abb.com/searchchannels.

Product training

For information on ABB product training, navigate to new.abb.com/service/training.

Providing feedback on ABB manuals

Your comments on our manuals are welcome. Navigate to new.abb.com/drives/manuals-feedback-form.

Document library on the Internet

You can find manuals and other product documents in PDF format on the Internet at abb.com/drives/documents.

abb.com/drives

© Copyright 2022 ABB. All rights reserved.

Specifications subject to change without notice.

3AUA0000114058 Rev C (EN) 2022-01-05

因篇幅问题不能全部显示,请点此查看更多更全内容

Copyright © 2019- huatuo0.com 版权所有 湘ICP备2023021991号-1

违法及侵权请联系:TEL:199 1889 7713 E-MAIL:2724546146@qq.com

本站由北京市万商天勤律师事务所王兴未律师提供法律服务